Rockwell-automation 1769-BOOLEAN Compact I/O Module Reference Manual Instrukcja Użytkownika Strona 53

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 98
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 52
Publication 1769-RM016A-EN-P - July 2006
Module Data, Status, and Configuration 53
The following table shows the bits patterns to use to configure the operands.
Bits Patterns Used to Configure the Operands
The default value for each operand is all 0's which corresponds to an operand
selection of None.
Words 9,10,11, 17,18,19, 25,26,27, 33,34,35 Operand
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
000000 None
0 0 0 0 0 1 Real Input 0
0 0 0 0 1 0 Inverted Real Input 0
0 0 0 0 1 1 Real Input 1
0 0 0 1 0 0 Inverted Real Input 1
0 0 0 1 0 1 Real Input 2
0 0 0 1 1 0 Inverted Real Input 2
0 0 0 1 1 1 Real Input 3
0 0 1 0 0 0 Inverted Real Input 3
0 0 1 0 0 1 Real Input 4
0 0 1 0 1 0 Inverted Real Input 4
0 0 1 0 1 1 Real Input 5
0 0 1 1 0 0 Inverted Real Input 5
0 0 1 1 0 1 Real Input 6
0 0 1 1 1 0 Inverted Real Input 6
0 0 1 1 1 1 Real Input 7
0 1 0 0 0 0 Inverted Real Input 7
0 1 0 0 0 1 Virtual Input 0
0 1 0 0 1 0 Inverted Virtual Input 0
0 1 0 0 1 1 Virtual Input 1
0 1 0 1 0 0 Inverted Virtual Input 1
0 1 0 1 0 1 Virtual Input 2
0 1 0 1 1 0 Inverted Virtual Input 2
0 1 0 1 1 1 Virtual Input 3
0 1 1 0 0 0 Inverted Virtual Input 3
0 1 1 0 0 1 Virtual Input 4
0 1 1 0 1 0 Inverted Virtual Input 4
0 1 1 0 1 1 Virtual Input 5
0 1 1 1 0 0 Inverted Virtual Input 5
0 1 1 1 0 1 Virtual Input 6
0 1 1 1 1 0 Inverted Virtual Input 6
0 1 1 1 1 1 Virtual Input 7
1 0 0 0 0 0 Inverted Virtual Input 7