Publication 20P-IN055A-EN-P
PowerFlex® DC Drive
Frame D Field SCR Module
Installation Instructions
What This Kit Includes
Field SCR module
Gate lead cables (2)
Screws and washers (2)
Thermal grease
Static strap
Important:It is highly recommended that the field circuit board and field dual
diode module be replaced when replacing the field SCR module.
The field circuit board and field dual diode module are sold as
separate spare part kits.
Tools That You Need
Phillips
®
screwdriver
Hexalobular screwdriver
Phillips
®
is a registered trademark of Phillips Screw Company.
ATTENTION: Only qualified personnel familiar with DC drives
and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply
may result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, ensure that all
power to the drive has been removed before performing the following.
ATTENTION: This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are required
when installing, testing, servicing or repairing this assembly.
Component damage may result if ESD control procedures are not
followed. If you are not familiar with static control procedures,
reference A-B publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection
handbook.
Przeglądanie stron 0
1 2 3 4 5 6 7 8

Podsumowanie treści

Strona 1 - Installation Instructions

Publication 20P-IN055A-EN-PPowerFlex® DC DriveFrame D Field SCR ModuleInstallation InstructionsWhat This Kit Includes• Field SCR module• Gate lead cab

Strona 2 - Protective Covers

Publication 20P-IN055A-EN-P2What You Need to DoTo install the field SCR module:❐ Step 1: Remove power from the drive❐ Step 2: Remove the protective co

Strona 3 - Figure 1 Cover Removal

3Publication 20P-IN055A-EN-PImportant:A communication cable connects the HIM assembly to the Control board mounted on the control pan. Therefore, the

Strona 4 - Step 3: Remove the Field

Publication 20P-IN055A-EN-P44. Disconnect the HIM communication cable from the connector on the upper right corner of the Control board and remove the

Strona 5 - Publication 20P-IN055A-EN-P

5Publication 20P-IN055A-EN-PImportant: Mark all connections and wires before removal to avoid incorrect wiring during reassembly.2. Disconnect the cab

Strona 6 - Existing Field SCR Module

Publication 20P-IN055A-EN-P6Step 4: Remove the Existing Field SCR Module1. Disconnect the gate lead wires from the connectors at the top of the SCR mo

Strona 7 - Step 6: Install the Field

7Publication 20P-IN055A-EN-P2. Remove the two screws and washers that secure the SCR module to the heatsink and remove the module.Figure 4 Field SCR

Strona 8 - Related Documentation

Publication 20P-IN055A-EN-P - May 2010Copyright © 2010 Rockwell Automation. All rights reserved. Printed in USA.www.rockwellautomation.comAmericas: Ro