2-10 Installing the Adapter
Table 2.B Drive and Adapter Start-Up Status Indications
Verifying/Setting Key Adapter Parameters
For instructions to use an optional PowerFlex 4-Class HIM to access
adapter parameters, see Using the Optional, External PowerFlex 4-Class
HIM on page 3-2.
1. Verify that adapter Parameter 08 - [MAC Address] is reporting the
MAC address set in Setting the MAC Address on page 2-2.
2. Set adapter Parameters 11 - [Device Inst Hi] and 12 - [Device Inst
Lo] to establish a unique number for representation to the Building
Automation Controller. For more information, see Setting the Device
Instance Number on page 3-4.
3. Reset the adapter by setting adapter Parameter 01 - [Reset Module]
to “1” (Reset Module) to apply the new Device Instance Number.
Configuring/Verifying Key Drive Parameters
The PowerFlex 4-Class drive can be separately configured for the control
and reference functions in various combinations. For example, you
could set the drive to have its control come from a peripheral or terminal
block with the reference coming from the BACnet MS/TP network. Or
you could set the drive to have its control come from the BACnet MS/TP
network with the reference coming from another peripheral or terminal
block. Or you could set the drive to have both its control and reference
come from the BACnet MS/TP network.
Item Name Color State Description
Drive FAULT Status Indicator
FAULT Red Off Drive ready but not running, and no faults are present.
Flashing A fault has occurred.
Adapter Status Indicators
PORT Green Flashing Normal Operation. The adapter is establishing
communications with the drive. It will turn solid green or red.
Steady Normal Operation. The adapter is properly connected and
communicating with the drive
MOD Green Flashing Normal Operation. The adapter is operating but is not
transferring I/O data.
Steady Normal Operation. The adapter is operating and transmitting
I/O data.
NET A Green Flashing Normal Operation. The adapter is properly connected and
communicating on the network.
NET B Green Off Normal Operation. The adapter is properly connected but is
idle.
Flashing Normal Operation. The adapter is transmitting data.