Publication 900-UM004D-EN-E - July 2010
2-20 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)
Command Code and related information
Response code
Normal Completion
Table 2.27
Command
Code
Description Related Information
00 Communications writing 00: OFF (disabled)
01: ON (enabled)
01 RUN/STOP 00: Run
01 : Stop
02 Multi-SP 00: Set point 0
01 : Set point 1
02: Set point 2
03: Set point 3
03 AT execute/cancel 00: AT Cancel
01 : 100% AT execute
02: 40% AT execute
04 Write mode 00: Backup mode
01 : RAM write mode
05 Save RAM data 00
06 Software reset 00
07 Move to setup area 1 00
08 Move to protect function
group
00
09 Auto/manual switch 00: Automatic mode
01: Manual mode
0B Parameter initialization 00: Initialize to defaults
0C Alarm Latch Cancel 00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: OC alarm latch cancel
0F: All alarm latch cancel
0E Invert Direct/Reverse
Operation
00: Not invert
01: Invert
11 Program start 00: Reset
01: Start
Table 2.28
Response
Code
Name Description
0000 Normal completion No errors were found.