Publication 900-UM004D-EN-E - July 2010
3-2 Communications Data
Not displayed on the controller’s display
When the variable type is 80 (word access), the rightmost 16 bits are read.
When the variable type is 80 (word access), the leftmost 16 bits are read.
Table 3.1 Variable Type C0 (80)
Variable
Ty pe
Address Item (Parameter)
Name
Set (monitor) Value Function
Group
C0 (80) 0000 Process value Temperature: Follow the specified range of the sensor. Operation
Analog: Scaling lower limit -5%FS to scaling upper limit +5%FS
C0 (80) 0001 Status➊➋ Refer to Status Structure on page 3-13
C0 (80) 0002 Internal set point SP lower limit to SP upper limit
C0 (80) 0003 Heater current 1 value
monitor
H’00000000…H’00000226 (0.0…55.0)
C0 (80) 0004 MV monitor (heating) Standard : H’FFFFFFCE…H’0000041A (-5.0…105.0)
Heating and cooling: H’00000000…H’0000041A (0.0…105.0)
C0 (80) 0005 MV monitor (cooling) H’00000000…H’0000041A (0.0 …105.0)
C0 (80) 0006 Heater current 2 value
monitor
H’00000000…H’00000226 (0.0…55.0)
C0 (80) 0007 Leakage current 1
monitor
H’00000000…H’00000226 (0.0…55.0)
C0 (80) 0008 Leakage current 2
monitor
H’00000000…H’00000226 (0.0…55.0)
C0 (80) 0009 Soak time remain H’00000000…H’0000270F (0…9999)
C0 (80) 000C Multi-SP monitor H’00000000…H’0000270F (0…3)
C0 (80) 000E Decimal Point
monitor
H’00000000…H’0000270F (0…3)
C0 (80) 000F Control Output 1
ON/OFF Count
Monitor
H’00000000…H’0000270F (0…9999)
Advanced
Function
C0 (80) 0010 Control Output 2
ON/OFF Count
Monitor
H’00000000…H’0000270F (0…9999)
C0 (80) 0011
Status 2 ➊➋ Refer to Status Structure on page 3-13
Operation
C0 (80) 0012
Status ➊➌ Refer to Status Structure on page 3-13
C0 (80) 0013
Status 2 ➊➌ Refer to Status Structure on page 3-13
Table 3.2 Variable Type C1 (81)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
C1 (81) 0000 Operation/adjustmen
t protection
H’00000000(0) No restrictions in Operation and
Adjustment function groups
H’00000001(1) Move to Adjustment function group
restricted
H’00000002(2) Display and change of only PV" and
PV/SP parameters enabled
H’00000003(3) Display of only PV and PV/SP parameters
enabled
Protect
C1 (81) 0001 Initial setting/
communications
protection
H’00000000(0) Move to Initial Setting/Communications
Setting function group enabled (move to
Advanced Setting function group
displayed)
H’00000001(1) Move to Initial Setting/Communications
Setting function group enabled (move to
Advanced Function Setting function
group not displayed)
H’00000002(2) Move to Initial Setting/Communications
Setting function group restricted
C1 (81) 0002 Setup change
protection
H’00000000(0) OFF (changing of setup on controller
display enabled)
H’00000001(1) ON (changing of setup on controller
display disabled)