Publication 1203-5.13 February, 2002
1203-CN1 Module Parameters B-3
7
DataLnk C Config
0 = Disabled
1 = Enabled
0=Disabled Yes Yes Determines whether to pass control data contained in
datalink C from a ControlNet connection to the
SCANport product.
8
DataLnk D Config
0 = Disabled
1 = Enabled
0=Disabled Yes Yes Determines whether to pass control data contained in
datalink D from a ControlNet connection to the
SCANport product.
9
Idle Flt Action
0 = Fault
1 = Zero Data
2 = Hold Last
3 = Fault Cfg
0=Fault Yes No Determines the action the module should instruct the
SCANport product to take if the module detects that
the PLC is set to program mode.
!
ATTENTION: Risk of severe bodily injury or loss of
life exists. The
Idle Flt Action
(9) parameter allows the
user to change the default configuration that would
allow the module and associated drive to continue to
operate if communication is lost. Precautions should
be taken to assure that your settings for these
parameters and your application do not create a
hazard of bodily injury or loss of life.
10
Comm Flt Action
0 = Fault
1 = Zero Data
2 = Hold Last
3 = Fault Cfg
0=Fault Yes No Determines the action the module should instruct the
SCANport product to take if the module detects a
network failure.
!
ATTENTION: Risk of severe bodily injury or loss of
life exists. The
Comm Flt Action
(10) parameter allows
the user to change the default configuration that would
allow the module and associated drive to continue to
operate if communication is lost. Precautions should
be taken to assure that your settings for these
parameters and your application do not create a
hazard of bodily injury or loss of life.
11
Fault Cfg Logic
0 65535 0 Yes No Provides the logic command data to the SCANport
product when the module is instructed to use the
values for the Fault Cfg parameters.
12
Fault Cfg Ref
0 65535 0 Yes No Provides the analog reference data to the SCANport
product when the module is instructed to use the
values for the Fault Cfg parameters.
13
Fault Cfg A1 In
0 65535 0 Yes No Provides the first word of datalink A data to the
SCANport product when the module is instructed to
use the values for the Fault Cfg parameters.
14
Fault Cfg A2 In
0 65535 0 Yes No Provides the second word of datalink A data to the
SCANport product when the module is instructed to
use the values for the Fault Cfg parameters.
15
Fault Cfg B1 In
0 65535 0 Yes No Provides the first word of datalink B data to the
SCANport product when the adapter is instructed to
use the values for the Fault Cfg parameters.
#Name
Valid Values/
Settings
Default Writable
Reset or
Power Cycle
to Take Effect
Description
Important: For information on accessing and editing parameters, refer to Chapter 3,
Getting Started.