Publication 1405-IN001B-EN-P - October 2003
6 Bulletin 1405 (M610) Operating Instructions
Dimensions
Panel cut-outs should be 92 x 92 mm (3.6 x 3.6 in).
Specifications
Table 1 Measured Parameters
Voltage V
L1 - L2
/ V
L2 - L3
/ V
L3-L1
V
L1 - N
/ V
L2 - N
/ V
L3-N
Instantaneous Current
Average Current (15 min.)
Peak Current
I
L1
/ I
L2
/ I
L3
Measuring Rate Approximately 2 measurements per second
Update Time 1.5 Seconds
Table 2 Digital Displays
Type 7 Segment LED, Red
Lines x Characters 3 x 4
Character Height 14 mm (0.55 in)
Table 3 General Parameters
Parameter Value
Nominal Voltage Per Catalog Version
Units with separate 120V or 240V supply: 600V
Units powered from 400V measurement line: 400V
Units powered from 480V measurement line: 480V
Voltage Range 0.8 V to 1.1V * (nominal voltage)
Current Range 0.0 A to 6.0 A