Q-Frame Circuit Breaker
Instruction Leaflet for Installation of Q-Frame Circuit Breakers
A
WARNING
CONTACT WITH ENERGIZED EQUIPMENT CAN
RESULT IN DEATH, SEVERE PERSONAL INJURY,
OR
SUBSTANTIAL PROPERTY DAMAGE. DO NOT
NANCE ON EQUIPMENT WHILE IT
IS
ENERGIZED.
ALWAYS VERIFY THAT NO VOLTAGE
IS
PRESENT
BEFORE PROCEEDING WITH THE TASK, AND
ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY
PROCEDURES.
ATTEMPT TO INSTALL
OR
PERFORM MAINTE
-
ALLEN-BRADLEY
IS
NOT LIABLE FOR THE MISAP
-
PLICATION
OR
MISINSTALLATION OF ITS
PRODUCTS.
The user is cautioned to observe all recommendations,
warnings, and cautions relating to the safety of personnel
and equipment as well as all general and local health and
safety laws, codes, and procedures. The recommenda
-
tions and information contained herein are based on
Allen-Bradley experience and judgement, but should not
be considered to be
all-inclusive or covering every appli
-
cation or circumstance which may arise. If any questions
Fig.
1
-
1
Q
-
Frame Circuit Breaker
Frame with Trip Unit Installed
arise, contact Allen-Bradley for further information or
instructions.
1.
INTRODUCTION
General Information
The Q
-
Frame circuit breaker (Fig.
1
-
1)
are 600 Vac maximum rated devices with
interchangeable thermal
-
magnetic or electronic
trip units rated 600A maximum continuous
current. The circuit breaker uses noninterchanageable
trip units and is factory sealed.
Refer to Table 1-1 for all available trip unit ratings.
This instruction leaflet (IL) gives procedures for installa
-
tion and field testing of Q
-
Frame circuit breakers.
For this publication, the term circuit breaker shall also
include the molded case switch.
100
Percent Rated L
-
Frame Circuit Breakers
Q-Frame circuit breakers are suitable for conrtinuous
operation at 100 percent of the frame rating
if
used with 90°C insulated wire and AL9CU
terminals in an
enclosure which measures at least 24
"
high x 15
"
wide x
6
"
deep. The minimum required ventilation is 8 sq. in. top
front and 8 sq. in. bottom front.
2.
INSTALLATION
The installation procedure consists of inspecting the cir
-
cuit breaker and, as applicable, installing the trip unit and
rating plug, accessories, and terminals; mounting the cir
-
cuit breaker; connecting the line and load conductors;
torquing terminals; and attaching terminal shields. Circuit
breaker frames, trip units, rating plugs, accessories,
mounting hardware, and unmounted terminals may be
Bul. 140U
40752-078(1) Effective 5/02
supplied in separate packages. To install the circuit
breaker, perform the following steps.
Przeglądanie stron 0
1 2 3 4 5 6 7 8

Podsumowanie treści

Strona 1 - Q-Frame Circuit Breaker

Q-Frame Circuit BreakerInstruction Leaflet for Installation of Q-Frame Circuit BreakersA WARNING CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH,

Strona 2 - 40752-078(1) Effective 5/02

Page 2 Internal accessory installation in any type of circuit breaker should be done before the circuit breaker is mounted and connected. Refer to ind

Strona 3 - 40752-078(1) Effective

Page 3 Pan-Head Screws Pan-Head Screws (Installed before 1 and 140U-Q-TLA2 Cable Clamoina Termina Lu

Strona 4 - WARNING

Page 4 a CAUTION WHEN ALUMINUM CONDUCTORS ARE USED, THE APPLICATION OF A SUITABLE JOINT COMPOUND IS RECOMMENDED TO REDUCE THE POSSIBILITY OF TERMINAL

Strona 5

PUSH-TO-TRIP - I 1 I Thermal- Magnetic Trip Unit Magnetic - Amps “C Cat. Multiples of In. (In.) No. 2 / Page 5 Fig. 4-2 Trip Unit Magnetic Adjustment

Strona 6

Page 6 ues in multiples of the trip unit ampere rating (I,) as shown in Fig. 4-2. To adjust the setting, rotate each but- ton clockwise until arrow

Strona 7

Page 7 Circuit Breaker Types Q-FrameTABLE I: AVAILABLE TRIP UNIT RATINGS Trip Unit Types Fixed Thermal 300 350 400 450 500 600 Thermal-Magnetic@ A

Strona 8

Paae 8 310-350 (2) 400-500 (2) 250-350 (2) 410-600 4-410 (2) 95-1 50 185-240 120-1 50 120-300 25-1 20 TABLE II: TERMINAL TYPES 0008 Terminal Terminal