12 XM Dynamic Measurement Module
Publication
ICM-IN002A-EN-P - March 2009
Self-Test
The XM module performs a self-test when it powers up. The self-test includes
an LED test and a device test. During the LED test, the indicators will turn
on independently and in sequence for approximately 0.25 seconds.
The device test occurs after the LED test. The Module Status (MS) indicator
is used to indicate the status of the device self-test.
MS Indicator State Description
Flashing Red and Green Device self-test is in progress.
Solid Green or Flashing Green Device self-test completed successfully, and
the firmware is valid and running.
Flashing Red Device self-test completed, the hardware
is OK, but the firmware is invalid.
The firmware download is in progress.
Solid Red Unrecoverable fault, hardware failure, or Boot
Loader program may be corrupted.