DIN Rail Grounding Block
24V Common Grounding
24V to the XM module must be grounded. When two or more power supplies
power the XM system, ground the 24 V Commons at a single point, such as
the ground bus bar.
If it is not possible or practical to ground the -24Vdc supply, then it is
possible for the system to be installed and operate ungrounded. However, if
installed ungrounded then the system must not be connected to a ground
through any other circuit unless that circuit is isolated externally.
Connecting a floating system to a non-isolated ground could result in
damage to the XM module(s) and/or any connected device. Also, operating
the system without a ground may result in the system not performing to the
published specifications regards measurement accuracy and
communications speed, distance or reliability.
The 24V Common and Signal Common terminals are internally connected.
They are isolated from the Chassis terminals unless they are connected to
ground as described in this manual. See Wiring on
page 14 for terminal
assignments.