20 XM Dynamic Measurement Module Terminal Base
Publication
ICM-IN003D-EN-P - March 2013
Surge Transient Immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on power ports
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on signal ports
±2 kV line-earth (CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Certifications
Certifications
(1)
(when product is marked)
Description
c-UL-us UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File
E194810.
CE European Union 2004/108/EC EMC Directive, compliant
with:
EN 61326-1; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8,
Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres,
Protection "n" (II 3 G Ex nA IIC T4X Gc)
EN 60079-0; General Requirements (Zone 2)
Environmental Specifications
Attribute Value