Connecting Rod Adjustment Procedure
"ON" Position
Ê
Move disconnect handle to the "ON" position.
Ê
If switch does not fully close, return handle to "OFF" position.
Ê
Remove link spring hitch pin and disengage the connectiong rod from the primary link.
Ê
Turn connecting rod counter-clockwise (1 or more) full turns.
Ê
Re-engage connecting rod in primary link of handle, insert hitch pin and re-test
Ê
Repeat
Ê
-
Ê
as necessary.
Ê
Re-install link spring
"OFF" Position
Ê
Move disconnect handle to the "OFF" position.
Ê
If switch does not fully open, return handle to "ON" position.
Ê
Remove hitch pin and link spring, then disengage the connectiong rod from the primary link.
Ê
Turn connecting rod clockwise (1 or more) full turns.
Ê
Re-engage connecting rod in primary link of handle, insert hitch pin and re-test.
Ê
Repeat
Ê
-
Ê
as necessary.
Ê
Re-install link spring
1
2
Connecting
Rod
Hitch Pin
Primary Link
5
6
Drive Bar
2