Installation a nd Wiri ng 3-3
1503-UM052D-EN-P June 2013
OEM
The IntelliVAC may be ordered as an OEM component. This allows the
OEM to mount the components in a configuration most suitable to the
motor controller equipment layout. Care must be exercised to ensure the
IntelliVAC has adequate ventilation provided around it. Refer to Figure
3.2 for mounting the IntelliVAC. It is recommended that a minimum of
1.5 inches (38.1mm) of free air space be provided between the
IntelliVAC and any solid barrier above or below.
The OEM is responsible for controller fusing, motor overload protection,
control devices (eg. Start/Stop push buttons), and wiring between the
IntelliVAC and 1502 vacuum contactor (using optional wire harness).
Wiring and mounting for optional items, such as TDUV Capacitor, are
also the OEM’s responsibility. Refer to Figure 3.3 for basic connections.