Rockwell Automation Publication 1609-QS002A-EN-P - May 2014 29
Appendix C EtherNet/IP IO Data Mapping
Appendix C - EtherNet/IP IO Data Mapping
If you want to control the UPS device just over the UDP (I/O Connection)
Interface, it is sufficient to use the mapping described. This section describes
the mapping. The different mappings over different instances are selected
in the assembly class.
Configuration Assembly
(Instance 0x64)
Consumed (Output) Assembly
(Instance 0x65)
Instance 0x64 – Configure Assembly (14 Bytes)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0Configuration Revision Number
1 Sensitivity
High Bit
Sensitivity
Low Bit
Buzzer
Enable
AutoReboot
2 Low Voltage Transfer Point (low byte)
3 Low Voltage Transfer Point (high byte)
4 High Voltage Transfer Point (low byte)
5 High Voltage Transfer Point (high byte)
6 Shutdown Delay (low byte)
7 Shutdown Delay (high byte)
8Boot Delay (low byte)
9 Boot Delay (high byte)
10 External Battery Pack (low byte)
11 External Battery Pack (high byte)
Instance 0x65 –Consumed (Output) Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Restart Bit ShutDown Bit SilenceAlarm
1 Perform Test Procedure
2 Shutdown Seconds (low byte)
3 Shutdown Seconds (high Byte)
4Restart Seconds (low byte)
5 Restart Seconds (high byte)
Przeglądanie stron 28
1 2 ... 24 25 26 27 28 29 30 31