30 Rockwell Automation Publication 1609-UM007A-EN-P - January 2013
Bulletin 1609 UPS Management Software User Manual
SNMP Trap Number
HTTP
1609 UPS Management Software supports WEB Server for remote manager to
obtain the UPS information. Users can use IE or Communicator to connect with
1609 UPS Management Service. Even your computer doesn't have 1609 UPS
Management Software installed you can monitor and control your UPS via
network.
Enable HTTP: Enable or disable the feature of Web service.
HTTP Root: The HTTP root path. All the html and gif files will be
located here.
Port Number: The default port number is 80 but if there is already one
WEB server running you can change 1609 UPS Management Service
HTTP port number to a different number. At the Internet Browser you
can input http://172.16.176.141:2000 in the URL where 2000 is the
assigned port number.
Variable Trap No. Description
dupsCommunicationLost 1 SEVER: Communication with the UPS failed
dupsCommunicationEstablished 2 INFORMATION: Communication with the UPS reestablished
dupsPowerFail 3 WARNING: Power failed! The UPS is operating on battery power
dupsPowerRestored 4 INFORMATION: Power restored! The utility power restored
dupsLowBattery 5 SEVER: The UPS batteries are low and will soon be exhausted
dupsReturnFromLowBattery 6 INFORMATION: The UPS has returned from a low battery condition
dupsLoadWarning 7 INFORMATION: Loading percent of the UPS over the Load Warning value
dupsNoLongerLoadWarning 8 INFORMATION: Returnd from Load Warning condition
dupsLoadSeverity 9 Warning: Loading percent of the UPS over the Load Severity value
dupsNoLongerLoadSeverity 10 INFORMATION: Returned from Load Severity condition
dupsUPSFault 13 SEVER: A general fault caused in the UPS
dupsBatteryGroundFault 14 SEVER: The UPS battery ground faul
dupsNoLongerBatteryFault 15 INFORMATION: The UPS recovered from battery ground fault
dupsTestInProgress 16 INFORMATION: The UPS test in progress
dupsBatteryTestFail 17 SEVER: The UPS test in progress
dupsFuseFailure 18 SEVER: The UPS fuse failed
dupsFuseRecovered 19 INFORMATION: The UPS fuse recovere
dupsOutputOverload 20 SEVER: The UPS overload
dupsNoLongerOverload 21 INFORMATION: Recovered from UPS overload
dupsOutputOverCurrent 22 SEVER: The UPS output overcurrent
dupsNoLongerOutputOverCurrent 23 INFORMATION: Recovered from UPS overcurrent
dupsInverterAbnormal 24 SEVER: The UPS inverter abnorma
dupsInverterRecovered 25 SEVER: Recovered from UPS inverter abnorma
dupsRectifierAbnormal 26 SEVER: The UPS rectifier abnormal
dupsRectifierRecovered 27 INFORMATION: The UPS recovered from rectifier abnormal
dupsReserveAbnormal 28 SEVER: The UPS rectifier abnorma
dupsReserveRecovered 29 INFORMATION: The UPS rectifier abnormal
dupsLoadOnReserve 30 INFORMATION: The UPS load on reserve
dupsNoLongerLoadOnReserve 31 INFORMATION: The UPS no longer load on reserve
dupsEnvOverTemperature 32 WARNING: The environment overtemperature
DupsNoLongerEnvOverTemperature 33 INFORMATION: The environment recovered from overtemperatur
DupsEnvOverHumidity 34 WARNING: The environment overhumidit
DupsNoLongerEnvOverHumidity 35 INFORMATION: The environment recovered from overhumidity