1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 21
Publication 1732E-IN005B-EN-E - September 2012
Input range
RTD type Temperature
Range (°C)
Voltage Range
100
Pt 385 0…390.48 -200…850 °C 0…156.25 mV
200
Pt 385 0…781
-200…850 °C 0…312.5 mV
100
Pt 3916 0…337.03 -200…630 °C 0…156.25 mV
200
Pt 3916 0…674.06 -200…630 °C 0…312.5 mV
10
Cu 427 0…19.116 -320…500 °C 0…19.53 mV
120
Ni 672 0…445.10 -70…445 °C 0…156.25 mV
100
Ni 618 0…198.88 -60…180 °C 0…78.125 mV
120
Ni 618 0…238.65 -90…140 °C 0…78.125mV
Accuracy 0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature
30 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration Factory calibrated. Calibration is also supported through RSLogix 5000.
Sample Rate
Filters
(1)
50 Hz
60 Hz
250 Hz
500 Hz
Common Mode
Rejection Ratio
120 dB @ 50/60 Hz
Normal Mode
Rejection Ratio
100 dB @ 50/60 Hz
(1)
Sample rate filter selectable on a module basis only.
Input Specifications – 1732E-IR4IM12R
Attributes Value