112 Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
Appendix C Data Tables
8 ProgMode
Ch7
ProgMode
Ch6
ProgMode
Ch5
ProgMode
Ch4
ProgMode
Ch3
ProgMode
Ch2
ProgMode
Ch1
ProgMode
Ch0
9 Reserved (Ignored)
10 ProgVal
Ch7
ProgVal
Ch6
ProgVal
Ch5
ProgVal
Ch4
ProgVal
Ch3
ProgVal
Ch2
ProgVal
Ch1
ProgVal
Ch0
11 Reserved (Ignored)
12…15 Hold Last State Duration [0]
16…19 Hold Last State Duration [1]
20…23 Hold Last State Duration [2]
24…27 Hold Last State Duration [3]
28…31 Hold Last State Duration [4]
32…35 Hold Last State Duration [5]
36…39 Hold Last State Duration [6]
40…43 Hold Last State Duration [7]
Where: ProgToFaultEn – Selects whether (enabled) or not (disabled) to apply the fault value when the output is already being set to
the program value when a Fault (connection timeout) occurs in Program Mode.
FaultMode – If Fault occurs (connection loss): When clear use FaultValue for Output. When set, Output Holds Last State for
HoldLastStateDuration.
Fault Value – If corresponding FaultMode bit clear, defines Output Value on Fault (connection timeout). Not used if FaultMode
bit is set.
Hold Last State Duration – If FaultMode is set (Hold Last State), this value determines the length of time the last state is to
be held prior to the FaultFinalState being applied. Valid values are 0 = Hold Forever, and either 1, 2, 5, or 10 (indicating hold
time in seconds). All other values reserved.
FaultFinalState – If FaultMode is set (Hold Last State) and HoldLastStateDuration[8] is non-zero, determines the final Output
state after the configured time out occurs.
ProgMode – If ProgramMode event occur: When clear use ProgValue for Output.
When set, Output Holds Last State.
ProgValue – If corresponding ProgMode bit clear, defines Output value on Program Mode.
Not used if ProgMode bit set.
Consumed Assembly Instance 174 Data Structure
Consumed
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Data Ch7 Data Ch6 Data Ch5 Data Ch4 Data Ch3 Data Ch2 Data Ch1 Data Ch0
1 Reserved (Ignored)
2 ScheduleMa
sk
Ch7
Schedule
Mask
Ch7
Schedule
Mask
Ch7
Schedule
Mask
Ch7
Schedule
Mask
Ch7
Schedule
Mask
Ch7
Schedule
Mask
Ch7
Schedule
Mask
Ch0
3 Reserved (Ignored)
4 Timestamp Offset
5 Schedule Timestamp
6 Schedule[0].ID
7 Schedule[0].SequenceNumber
8 Schedule[0].OutputPointSelect
9 Schedule[0].Data
Configuration Assembly Instance 171 Data Structure
Consumed
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Komentarze do niniejszej Instrukcji