Rockwell-automation 1734-ACNR POINT I/O ControlNet Adapter User Manual Instrukcja Użytkownika Strona 21

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 110
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 20
1 Publication 1734-UM008B-EN-P - August 2005
Chapter
3
Plan to Use Your Adapter
Chapter Objectives
This chapter explains how the adapter operates on a ControlNet
network and provides information to assist in configuring your
system. This chapter contains the following information.
Overview of adapter operation
I/O connections
Rack connections
Direct connections
Explicit messaging communications
Software requirements
Understanding ControlNet I/O
Scheduled data-transfer connections on a ControlNet network
Overview of
Adapter Operation
Connections are established between a scanner and an adapter to
exchange input and output data on the network. Status information is
transferred along with the I/O data.
I/O Connections
The adapter supports 25 direct and 5 rack I/O connections to the
POINT I/O modules. From a single 1734-ACNR adapter, multiple
controllers can establish I/O connections, up to a maximum of 5 rack
I/O connections per adapter. You must use direct connection with
analog and specialty I/O modules.
Make multiple rack connections to permit multiple controllers to
connect to I/O over a single 1734-ACNR adapter.
The number of connections that can actually be supported on a
network depends on the following.
ControlNet parameters (NUT, RPI, API)
POINT I/O configuration by itself (number and types of
modules)
Type of connection to these modules (direct connection, rack
connection)
Przeglądanie stron 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 109 110

Komentarze do niniejszej Instrukcji

Brak uwag