22 POINT I/O DeviceNet Adapter
Publication
1734-IN026A-EN-P - April 2005
Communications Interface Specifications (continued)
Expansion I/O Capacity Up to 13 modules (13 times 75mA = 0.975, just under the
limit of 1.0A), based on POINTBus current requirements
The actual number of modules can vary. Add up the current
requirements of the modules you want to use to make sure
they do not exceed the amperage limit of the adapter. Total
expansion is up to 63 modules - 13 modules maximum with
the adapter. Add 1734-EP24DC modules for an additional
17 modules (or less based on current requirements), up to
63 modules maximum.
Cat. No. PointBus Current Requirements
1734-IB2 75mA
1734-IB4 75mA
1734-IB8 75mA
1734-IV2 75mA
1734-IV4 75mA
1734-OB2 75mA
1734-OB4 75mA
1734-OB8 75mA
1734-OB2E 75mA
1734-OB2EP 75mA
1734-OB4E 75mA
1734-OB8E 75mA
1734-OV2E 75mA
1734-OV4E 75mA
1734-OW2 80mA
1734-OX2 100mA
1734-IE2C 75mA
1734-OE2C 75mA
1734-IE2V 75mA
1734-OE2V 75mA
1734-IA2 75mA
1734-IM2 75mA
1734-OA2 75mA
1734-IJ2 160mA
1734-IK2 160mA
1734-IR2 220mA
1734-IT2I 175mA
1734-SSI 110mA
1734-VHSC5 180mA
1734-VHSC24 180mA
1734-232ASC 75mA