Rockwell-automation 1734-AENTR POINT I/O 2 Port EtherNet/IP Adapter Instrukcja Użytkownika Strona 17

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 28
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 16
POINT I/O 2 Port Ethernet Adapter 17
Publication
1734-IN040B-EN-P - December 2009
Interpret the Status Indicators
Indicator State Description
Module
status
Off No power applied to device
Solid green Device operating normally
Flashing
red/green
Module self-test
Flashing red Recoverable fault.
Complete firmware update, verify address switches.
Solid red Unrecoverable fault, may require device replacement
Network
status
Off Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing green Device is on-line but has no CIP connections in the
established state.
Solid green Device on-line and has CIP connections in the established
state.
Flashing red One or more CIP connections in timed-out state.
Check for I/O module failure and controller operation.
Solid red Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing
red/green
Module self-test
Przeglądanie stron 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 27 28

Komentarze do niniejszej Instrukcji

Brak uwag