Publication 1734-UM006B-EN-P - August 2005
A-6 Configure Modules in RSLogix 5000 Software
3. Refer to the table to make selections for the following entries.
Store Count Mode
Rollover
Preset
Counter Attenuator
Frequency Precision
Gate Multiplier
Time Base
Actual Gate Interval
If You Selected This for Type For This Value Select Comments
Counter (default)
Encoder X1
Encoder X2
Encoder X4
Store Count
Mode
Store Count Disabled
Store-Continue
Store-Wait-Resume
Store, Reset-Wait-Start
Store, Reset-Start
Default is Store Count Disabled.
Select an option to determine which mode you use
for operating the Z Gate/Reset Terminal,
Rollover 1 to 16777216 Default is 16777215.
Select a value greater than the value for Preset.
Preset 0 to 16777215 Default is 0.
Select a value smaller than the value for Rollover.
Counter
Attenuator
0 to 255 Default is 1.
Select a value to attenuate the counter display.
Period/Rate
Rate Measurement
Frequency
Precision
X 0.0001
X 0.001
X 0.01
X 0.1
X 1
X 10
X 100
Default is X1.
Select a value to multiply the frequency by the factor
selected.
Gate Multiplier 1 to 200 Default is 1.
Select a value so that the product of Gate Multiplier
and Time Base does not exceed 3 seconds
(3000 milliseconds).
Time Base 10 to 3000 milliseconds
in multiples of 10
Default is 1000.
Actual Gate
Interval
You do not make a
selection, as this is a static
field you do not configure.
This is the product of Gate Multiplier and Time Base.
An acceptable value is less than 3 seconds
(3000 milliseconds).