Rockwell-automation 1747-DU501 SLC 5/05 Processors Firmware/Operating Instrukcja Użytkownika Strona 7

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 20
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 6
SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 7
Publication 1747-IN019G-EN-P - December 2011
8. Select the appropriate catalog number from the Catalog Number dialog box and click Next.
For Series C Processors, select catalog numbers that are followed by a ‘/C.
The AB_SNMP.DLL – Enter IP Address dialog box appears.
9. Enter the IP address for the processor.
IMPORTANT
Use the IP address that was noted in step 2 of the section, Prior to Running
ControlFLASH on page 3. If the processor has been reset to Initial Factory
Conditions, use an available IP address assigned by your network administrator.
Przeglądanie stron 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 19 20

Komentarze do niniejszej Instrukcji

Brak uwag