6–80 Library of Routines OC_WaitForEosDmdIn
Publication 1747-6.5.3 June 1998
OC_WaitForEosDmdIn Blocks the calling thread until a demand input end-of-scan (EOS) notification is
received from the scanner or
msTimeout milliseconds have elapsed.
Syntax:
int OC_WaitForEosDmdIn(HANDLE handle, DWORD msTimeout)
Parameters:
Description:
If a demand input EOS message has been received since the last OCMSG_EOS_DMDIN message was
retrieved with the OC_PollScanner function, OC_WaitForEosDmdIn returns SUCCESS immediately.
You can use this function to synchronize a control application with the I/O scan. See the
OC_EnableEOSNotify and OC_DemandInputScan functions.
Return Value:
Considerations:
Supported in the Windows NT API library only.
Parameter: Description:
handle
Must be a valid handle returned from OC_OpenScanner
msTimeout
Specifies the number of milliseconds to wait
Set to INFINITE to wait forever
Name: Value: Description:
SUCCESS
0
demand input EOS message was received
ERR_RESPONSE
10
msTimeout milliseconds elapsed without an EOS
ERR_OCACCESS
2
handle does not have access to scanner