SynchLink Bypass Switch Block 13
Publication 1751-IN003B-EN-P - September 2001
Specifications
Power Supply To comply with CE Low Voltage directives, you must use a
Safety Extra Low Voltage (SELV) or a Protected Extra Low
Voltage (PELV) power supply to power this bypass switch block.
Use a NEC/CEC Class 2 power supply in order to comply with
UL and CSA requirements.
Power Supply Rating 0.1A @ 24V dc nominal
Power Supply Range 20V dc to 30V dc
A regulated power supply is recommended.
Communication Rate 5M bit/s
Terminal Block Torque Requirements 5-7 inch-pounds maximum
Environmental Conditions
Operating Temperature
0 to 60°C (32 to 140°F)
(1)
Storage Temperature
40 to 85°C (40 to 185°F)
(2)
Relative Humidity
5 to 95% non-condensing
(3)
Vibration
5g @ 10-500Hz
(4)
Shock
Operating 30g
(5)
Non-operating 50g
Emissions
Group 1, Class A
(6)
ESD Immunity
6kV contact discharges
(7)
8kV air discharges
Radiated RF Immunity
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
(8)
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity
±2kV at 5kHz on power ports
(9)
±2kV at 5kHz on signal ports
Surge Transient Immunity
+
2kV line-earth (CM) on shielded ports
(10)
Conducted RF Immunity
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
(11)
Enclosure Type Ratings 8.0 pt
Fiber Optic Cable
Fiber Type 200/230 micron HCS (Hard Clad Silica)
Fiber Termination Type Versalink V-System
Assemblies Cable assemblies can be ordered from Allen-Bradley, catalog
number 1403-CFxxx (xxx = length in meters); or from Lucent
Technologies, Specialty Fiber Technologies division.
Maximum Length 300 meters
Minimum Length 1 meter