Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Environmental Specifications – 1753-IB16 Module
Attribute 1753-L28BBB-M, 1753-L28BBB-P
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged nonoperating
cold)
IEC 60068-2-2 (Test Bb, Unpackaged nonoperating
dry heat)
IEC 60068-2-14 (Test Na, Unpackaged nonoperating
thermal shock)
-40…85 °C (-40…185 °F)
Temperature, operating
IEC 60068-2-1 (Test Ad, operating cold)
IEC 60068-2-2 (Test Bd, operating dry heat)
IEC 60068-2-14 (Test Nb, operating thermal shock)
0…60 °C (32…140 °F)
Temperature, surrounding air 60 °C (140 °F)
Vibration
IEC 60068-2-6 (Test Fc, operating)
1 g @ 10…150 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, unpackaged shock)
15 g
Relative humidity
IEC 60068-2-30 (Test Db, unpackaged damp heat)
10…95% noncondensing
Emissions CISPR 11: Group 1, Class A
ESD Immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1kHz sine-wave 80% AM from
80 MHz…2000 MHz
1 V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4
±2 kV @ 5 kHz on DC power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge Transient Immunity
IEC 61000-4-5
±500V line-line (DM) and ±500V line-earth (CM)
on DC power ports
±1 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on communication ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz
Damped Oscillatory Wave Immunity
IEC 61000-4-12
±1 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on power ports