When power is applied to the module, the alphanumeric display should cycle
through these states:
TEST
PA SS
OK
REV x.x
where x.x is the module’s firmware revision.
The display then alternates between OK and the module’s EtherNet/IP address.
Install or Remove the Module Under Power
You can install or remove this module while chassis power is applied.
1. Push on upper and lower module tabs to disengage them.
WARNING: When you insert or remove the module while
backplane power is on, an electrical arc can occur. This could
cause an explosion in hazardous location installations. Be sure
that power is removed or the area is nonhazardous before
proceeding. Repeated electrical arcing causes excessive wear to
contacts on both the module and its mating connector. Worn
contacts may create electrical resistance that can affect module
operation.