8 Compact I/O 1769-ADN DeviceNet Adapter
Rockwell Automation Publication 1769-IN001C-EN-P - February 2013
Where the “Number of Output Modules” is the number of output modules
configured to have 1 or more words of output data.
The maximum number of output words is distributed across all of the output
modules.
• The Series B adapter supports a maximum of 254 words (508 bytes) of configuration
data for each individual module, for a total capacity of 7,620 words (15,240 bytes). The
configuration data is stored within 1 (64K) sector of the external flash part, enabling the
maximum for each module to be supported, regardless of the number of modules.
• The Series A adapter supports a total of:
– 180 words of input data from the I/O modules.
– 180 words of output data from the I/O modules.
– 724 words of configuration data for the I/O modules.