The bits are defined as follows:
EC = Enable Channel
Inpt Dta Fm Chlx = Input Data Format Select
EA = Enable Alarm
AL = Alarm Latch
EI = Enable Interrupt
(1)
Inpt Tp/Rnge Sel Chlx = Input Type/Range Select
Inpt Filter Sel Chlx = Input Filter Select
Reserved = Allows for future expansion
ETS = Enable Time Stamp
24 S Alarm Dead Band Value Channel 3
25 Reserved
(1) MicroLogix 1500 and CompactLogix L3x controllers do not support interrupts.
Bit Definitions for Channel Configuration Words
Define To Select Make these bit settings
15 1411 10 9 8 743210
Input Filter Selection 60 Hz 0 0 0 0
50 Hz 0001
28.5 Hz 0 0 1 0
300 Hz 0 0 1 1
360 Hz 0 1 0 0
Enable Interrupt Enable 1
Disable 0
Enable Process
AlarmLatch
Enable 1
Disable 0
Enable Process
Alarms
Enable 1
Disable 0
Enable Channel Enable 1
Disable 0
Configuration Data Array (cont.)
Word
Bit Position
15 14131211109876543210