Installation and Wiring Chapter 2
System Wiring Guidelines
Consider the following when wiring your system:
All module commons (ANLG Com) are connected in the analog
module.
The analog common (ANLG Com) is not connected to earth
ground inside the module.
Channels are not isolated from each other.
For optimum accuracy, limit overall cable impedance by
keeping your cable as short as possible. Locate the I/O system
as close to your sensors or actuators as your application will
permit.
Use Belden 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire and shield junction
must be connected to earth ground via a panel or DIN-rail
mounting screw at the analog I/O module end.
(1)
Keep shield connection to ground as short as possible.
Voltage outputs (Vout 0+…Vout 3+) of the 1769-OF4 module are
referenced to ANLG Com. Load resistance for a voltage output
channel must be equal to or greater than 1 kΩ .
Current outputs (Iout 0+…Iout 3+) of the 1769-OF4 module
source current that returns to ANLG Com. Load resistance for a
current output channel must remain between 0 and 600 Ω .
(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cable
shields to earth at the module end and via a 0.01 µF, 2000V capacitor at the sensor end.