Compact 1769-OF8C Analog Output Module 15
Publication 1769-IN065C-EN-P - June 2010
E = Channel Enable: (0 = Disabled, 1 = output 0 and hold Enabled, process changes)
Reserved = Set to zero
SIU = System interrupt low clamp, under-range alarms: (0 = Disabled, 1 = Enabled)
SIO = System interrupt high clamp, over-range alarms: (0 = Disabled, 1 = Enabled)
LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled, 1 = Enabled)
ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by fault states.)
FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
PFE = Program/idle to fault enable: (0 = Disabled, 1 = Enabled)
Word Description Word Description
48 Channel 6 Configuration Word 0 56 Channel 7 Configuration Word 0
49 Channel 6 Configuration Word 1 57 Channel 7 Configuration Word 1
50 Channel 6 Fault Value Word 58 Channel 7 Fault Value Word
51 Channel 6 Program Idle Mode Word 59 Channel 7 Program Idle Mode Word
52 Channel 6 Low Clamp 60 Channel 7 Low Clamp
53 Channel 6 High Clamp 61 Channel 7 High Clamp
54 Channel 6 Ramp Rate 62 Channel 7 Ramp Rate
55 Channel 6 Spare 63 Channel 7 Spare
Word/Bit1514131211109876543210
Word 0 E Reserved SIU SIO LA ER FM PM HI PFE
Word 1 Reserved Output Data
Format Select
Reserved Output
Type/Range