Publication 1769-UM009E-EN-P - August 2009 51
Automatically Configure a DeviceNet Network Chapter 4
Initiate AutoScan via the 193-DNCT Terminal
Follow these steps to enable AutoScan using the 193-DNCT terminal, version
2.1 or higher.
1. Put your controller into Program mode, and verify that the scanner is in
Idle mode (CommandRegister.Run = 0) and that all slave nodes are
connected and communicating on the DeviceNet network.
2. Plug the 193-DNCT terminal into the DeviceNet network.
3. In the Network Who dialog, press <Up Arrow> to navigate to and
select the first line (0 - 1769-SDN DeviceNet Scanner).
4. Press <Enter> to go to the scanner’s configuration dialog.
5. Press <Down Arrow> to navigate to Scanner and press <Enter>
.
6. Press <Down Arrow> to navigate to AutoScan and press
<Enter> .
The AutoScan Setup dialog appears.
7. If AutoScan is selected and set to Enable, press <Up Arrow> to
change the setting to Disable.
8. Press <SEL> to scroll down to Save. This disable the AutoScan
feature.
9. Press <SEL> to scroll down to Mapping.
10. Type in the number of bytes that you want to automap to each
DeviceNet node, that is, 1…32. The default is 4 bytes.
11. Press <SEL> to scroll down to Save, and press <Enter> to
commit your byte size selections.
The AutoScan feature is now configured with the byte size entered in
step 9
and
step 10
. For the 1769-SDN scanner to remap the network with
this new setting, the AutoScan feature must be re-enabled.