Programming ExamplesB–4
!
2. Press [F8],[F5] and enter N7:60 to display the configuration
block.
The industrial terminal screen should like figure B.3.
Figure B.3
Sample PLC-5 Data File (Hexidecimal Data)
The above data file would configure the module as follow:
• copper RTDs on all inputs
• temperature scale of Fahrenheit
• channel 1 displayed in ohms
• output data in BCD format
• real time sampling set to a 1 second scan rate
• copper RTD at 25
o
C is 9.76 ohms
• all bias values set to subtract 0150
• all calibration values set to 0
3. Enter the data corresponding to your bit selections.
4. [ESC] returns you to the main menu.