Publication 1771-IN078A-EN-P - October 2002
AC (120V) Isolated Output
Module
(Catalog Number 1771-OD)
This document provides information on:
To See page
Important User Information 1
Pre-installation Considerations 4
Suppression 4
Calculate Power Requirements 5
Determine Module Placement 5
Prevent Electrostatic Discharge 5
Key the Backplane Connector 6
Install the Module and Field Wiring Arm 7
Connect Wiring to the Module 8
For this reference information See page
Interpreting the Status Indicators 10
Replacing a Fuse 10
Specifications 11
Because of the variety of uses for the products described in this
publication, those responsible for the application and use of these
products must satisfy themselves that all necessary steps have been
taken to assure that each application and use meets all performance
and safety requirements, including any applicable laws, regulations,
codes and standards. In no event will Rockwell Automation be
responsible or liable for indirect or consequential damage resulting
from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples
shown in this publication are intended solely for purposes of
example. Since there are many variables and requirements associated
with any particular installation, Rockwell Automation does not
assume responsibility or liability (to include intellectual property
liability) for actual use based upon the examples shown in this
publication.
Installation Instructions
To The Installer
Important User
Information
Przeglądanie stron 0
1 2 3 4 5 6 ... 11 12

Podsumowanie treści

Strona 1 - AC (120V) Isolated Output

Publication 1771-IN078A-EN-P - October 2002AC (120V) Isolated OutputModule(Catalog Number 1771-OD)This document provides information on:To See pageImp

Strona 2 - ATTENTION

AC (120V) Isolated Output Module10Publication 1771-IN078A-EN-P - October 2002The module has 12 status indicators (Figure 3). The top 6 indicatorsshow

Strona 3

AC (120V) Isolated Output Module 11Publication 1771-IN078A-EN-P - October 20024. Replace the blown fuse with a 5A, 250V Bussman MTH5, IEC127 Type F f

Strona 4 - Considerations

AC (120V) Isolated Output Module12Publication 1771-IN078A-EN-P - October 2002Fuses 5A, 250V Bussman MTH5, IEC 127 Type FField Wiring Arm Cat. No. 177

Strona 5 - Placement

AC (120V) Isolated Output Module2Publication 1771-IN078A-EN-P - October 2002Allen–Bradley publication SGI–1.1, Safety Guidelines forApplication, Inst

Strona 6 - Key the Backplane Connector

AC (120V) Isolated Output Module 3Publication 1771-IN078A-EN-P - October 2002ATTENTION!Environment and EnclosureThis equipment is intended for use in

Strona 7 - Wiring Arm

AC (120V) Isolated Output Module4Publication 1771-IN078A-EN-P - October 2002An output from this module can drive an Allen–Bradley Size 5motor starter

Strona 8 - Connect Wiring to the

AC (120V) Isolated Output Module 5Publication 1771-IN078A-EN-P - October 2002The isolated output module is powered by the power supplyconnected to th

Strona 9 - Figure 2

AC (120V) Isolated Output Module6Publication 1771-IN078A-EN-P - October 2002Key the Backplane ConnectorPlace your module in any slot in the chassisex

Strona 10 - Replacing a Fuse

AC (120V) Isolated Output Module 7Publication 1771-IN078A-EN-P - October 2002ATTENTION!Remove power from the 1771 I/O chassisbackplane and wiring arm

Strona 11 - Specifications

AC (120V) Isolated Output Module8Publication 1771-IN078A-EN-P - October 2002You make connections to the module through the 1771-WD fieldwiring arm sh

Strona 12 - PN957689-80

AC (120V) Isolated Output Module 9Publication 1771-IN078A-EN-P - October 2002You can use an output of the 1771–OD module to drive an input of a120V A