Publication 1771-IN081B-EN-P - June 2004
8 Isolated 24V dc Output Module
Interpreting the Status
Indicators
The front panel of your module contains 8 red status indicators (below). The
red status indicators are on when the associated output is on.
Replacing the Fuses
To replace a blown fuse, proceed as follows:
1. Turn off power to the chassis.
2. Remove the module from the I/O chassis.
3. Remove the 2 screws securing the front cover on the unlabelled side of
the module. Note: One fuse protects 2 outputs.
4. Remove the blown fuse from fuse holder, and replace with a 2.5A, 3AG
normal blow fuse.
5. Replace the cover and secure with screws removed in step 3.
6. Reinsert the module into I/O chassis.
7. Turn on power to chassis.
Not used
Output 0
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Status Indicators
1
1067-I
ATTENTION
Remove power from the 1771 I/O chassis backplane and
field wiring arm before removing or installing an I/O
module.
Failure to remove power from the backplane or wiring
arm could cause module damage, degradation of
performance, or injury.
Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.