Connect the Wiring to the ArmorBlock Module
This module uses quick disconnect, screw-on style connectors for:
I/O input wiring
the DeviceNet connector
30197–M
Eight 5-pin Input Micro-connectors
5-pin DeviceNet Mini-connector
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
1
2
3
4
56
7
8
Seven micro plugs are included with your module. Use these plugs to
cover and seal unused ports. Pinout diagrams for these connectors are
shown below.
!
ATTENTION: Make sure all connectors are securely
tightened to properly seal the connections against leaks and
maintain IP67 requirements.
Connecting the Input Wiring
Connect input wiring to the micro-connectors which screw into mating
connectors on the front of the block.
Make connections as shown below.
1
2
34
I/O Input Micro-Connector
Pin 1 = Sensor Source Voltage Positive
Pin 2 = Signal B
Pin 3 = Negative/Return
Pin 4 = Signal A
(View into socket)
5
Pin 5 = Ground
Use a splitter cable (or “Y” cable) to access signal B.