ArmorBlock MaXum 16 Input Module with Complete Diagnostics 15
Publication 1792D-IN053A-EN-P - August 2002
This product has been tested at an Open DeviceNet Vendor
Association, Inc. (ODVA) authorized independent test laboratory and
found to comply with ODVA Conformance Test. Please contact the
ODVA website (http://www.odva.org) for listing of products tested by
ODVA independent test labs for further details.
General Specifications (cont.)
EFT/B Immunity IEC 61000-4-4:
±4kV at 2.5kHz on signal ports
±4kV at 2.5kHz on power ports
±2kV at 5kHz on communications ports
Surge Transient Immunity ±500V line-line(DM) and ±500V line-earth(CM) on signal
ports
+
2kV line-earth (CM) on shielded ports
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Certifications
(when product is marked)
CSA CSA Certified Process Control Equipment
CSA CSA Certified Process Control Equipment for
Class I, Division 2 Group A,B,C,D Hazardous
Locations
CE
3
European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
3
Australian Radiocommunications Act, compliant
with:
AS/NZS 2064; Industrial Emissions
ODVA ODVA conformance tested to DeviceNet
specifications
Technical Data (user information) Publication 1792-TD001
1. You use this conductor category information for planning conductor routing as described in the
system level installation manual.
2. See publication 1770-4.1, “Programmable Controller Wiring and Grounding Guidelines.”
3. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.
16 Input Module - Cat. No. 1792D-16BVTOCD