6 ArmorBlock MaXum 8 Input / 8 Output Module Series B
Publication 1792D-IN020B-EN-P - September 2000
Use the micro caps to cover and seal unused ports. Pinout diagrams
for the connectors are shown next.
Please refer to publication 889-5.0 for Rockwell Automation cables
and cord sets offerings.
IMPORTANT
If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.
Input Micro-Connector
(View into Socket)
Pin 1 Sensor Source voltage
Pin 2 Input B
Pin 3 Return Logic Ground
1
Pin 4 Input A
Pin 5 Not Used
Output Micro-Connector
(View into Socket)
Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Ground
Pin 4 Output A
Pin 5 Not Used
41452
1
Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.