Publication 1794-IN087C-EN-P - July 2005
Node Address
Set the node address using the thumbwheel switches on the front of the
adapter. Valid settings range from 00 to 99. Use the + or - buttons to set the
node address.
GSD Requirements
Current functionality of PROFIBUS adapters requires GSD files. These files
are easy to install and are available online at: www.ab.com/networks/gsd.
Indicators
Thumbwheel switches for setting the node address.
Status Indicator
Indication Status
OFF No power
Solid Green Normal operation
Flashing Red/OFF Recoverable Fault
- FLEX I/O module defective
- Incorrect module installed
- Node address changed since
powerup
PROFIBUS Indicator
Indication Status
OFF No power or no communication
Solid Green Data is being transmitted and received
Flashing Red/OFF Recoverable Fault
- Invalid Send parameter data
- Invalid Check Configuration data
Solid Red Unrecoverable fault
- Unable to communicate
STATUS Indicator
(green/red)
PROFIBUS
Indicator
(green/red)