Installation InstructionsFLEX I/O Isolated Input HART Analog ModuleCatalog Number 1794-IF8IH Topic PageImportant User Information 2Environment and Enc
10 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Ground the ModuleAll I/O wiring must use shielded wire. Shie
FLEX I/O Isolated Input HART Analog Module 11Publication 1794-IN115C-EN-P - April 2009Module Wiring 0
12 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Wire ConnectionsChannel Signal Ty peLabel MarkingsCatalog N
FLEX I/O Isolated Input HART Analog Module 13Publication 1794-IN115C-EN-P - April 2009Input Map Word Bit15141312111098765432100 Channel 0 Input Da
14 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Configuration MapWord Bit15141312111098765432100RRF7F6F5F4BO
FLEX I/O Isolated Input HART Analog Module 15Publication 1794-IN115C-EN-P - April 200929…32Words 9…12 for channel 533…36Words 9…12 for channel 637
16 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Cn HART CMD 3 Disable 0: HART CMD 3 communications enabled1:
FLEX I/O Isolated Input HART Analog Module 17Publication 1794-IN115C-EN-P - April 20094.17 Hz 5 101Not applicable 6 1 1 0Not applicable 7 1 1 1HAR
18 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Channel Data FormatsFormat(1)Bits Format NameSignal Range Us
FLEX I/O Isolated Input HART Analog Module 19Publication 1794-IN115C-EN-P - April 2009Cyclic HART Input DataThe HART input data holds the primary
2 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Important User InformationSolid state equipment has operation
20 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009HART Input DataWord Bit15141312111098765432100 Reserved CH7C
FLEX I/O Isolated Input HART Analog Module 21Publication 1794-IN115C-EN-P - April 200950…61Words 2…13 for channel 462…73Words 2…13 for channel 574
22 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009HART Input Data descriptionsCHn: HART CMD 3 Communication St
FLEX I/O Isolated Input HART Analog Module 23Publication 1794-IN115C-EN-P - April 2009Status IndicatorThe OK status indicator is bicolor, red, and
24 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Normal mode rejection ratio - current terminal>70 dB @ 50
FLEX I/O Isolated Input HART Analog Module 25Publication 1794-IN115C-EN-P - April 2009Wiring category(3)2 on signal ports 3 on power portsWire typ
26 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Environmental Attribute ValueTemperature, operating IEC 6006
FLEX I/O Isolated Input HART Analog Module 27Publication 1794-IN115C-EN-P - April 2009EFT/B Immunity IEC 61000-4-4: ±3 kV at 5 kHz on signal ports
Publication 1794-IN115C-EN-P - April 2009 PN-44688Supersedes Publication 1794-IN115B-EN-P - October 2008 Copyright © 2009 Rockwell Automation, Inc. Al
FLEX I/O Isolated Input HART Analog Module 3Publication 1794-IN115C-EN-P - April 2009Environment and Enclosure ATTENTIONThis equipment is
4 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009Preventing Electrostatic Discharge ATTENTIONThis pro
FLEX I/O Isolated Input HART Analog Module 5Publication 1794-IN115C-EN-P - April 2009North American Hazardous Location Approval The following in
6 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 2009European Hazardous Location Approval European Zone
FLEX I/O Isolated Input HART Analog Module 7Publication 1794-IN115C-EN-P - April 2009Install the ModuleRead this for information about how to inst
8 FLEX I/O Isolated Input HART Analog Module Publication 1794-IN115C-EN-P - April 20093. Make sure the pins on the bottom of the module are straigh
FLEX I/O Isolated Input HART Analog Module 9Publication 1794-IN115C-EN-P - April 20093. Connect the +V DC power lead to terminal 34 on the 34…51 r