5
Publication 1794-IN050J-EN-P - January 2009
FLEX I/O and FLEX I/O-XT are trademarks of Rockwell Automation.
Accuracy vs. filter cutoff 0.05% of full range in millivolt mode with filtering selected
Hardware only = 0.10% of full range in millivolt mode
Data format °C (implied decimal point XXX.X)
°F (implied decimal point XXX.X)
°K (implied decimal point XXX.X)
-32767…32767
0…65535
0…5000 (ohms mode) (implied decimal point XXX.X)
-4000…+10000 (millivolt mode) (implied decimal point XXX.XX)
Common mode rejection -80 db @ 5V peak-to-peak, 50…60 Hz
Common mode input
range
+15V min
Isolation voltage
(continuous voltage
withstand rating)
50V (continuous), Basic Insulation Type
Type tested at 1365V AC for 60 s, between field side and system
No isolation between individual channels"
System throughput (8
channels scanned) - Add
0.5 ms if filtering is
selected
Typical module timing is shown here.
7.4 ms - millivolt
8.0 ms - Ω - 2-wire RTD
10.0 ms - Ω - 3-wire RTD
10.4 ms - Ω - 4-wire RTD
8.0 ms - 2-wire RTD (°F)
10.4 ms - 4-wire RTD (°F)
8.8 ms - 2-wire RTD (°C), (°K)
10.8 ms - 4-wire RTD (°C), (°K)
9.8 ms - 3-wire RTD (°F)
10.0 ms - 3-wire RTD (°C), (°K)
9.0 ms - Thermocouples (°F)
9.4 ms - Thermocouples (°C), (°K)
Open circuit protection RTD mode - Open input - Module defaults to max value
TC mode - Open input - Module defaults to min value
To simulate wire-off detection in Series A TC mode when using a Series B
module, attach a jumper from terminal 39 to terminal 48 on the 1794-TB3G,
1794-TB3GS, or 1794-TB3GK terminal base unit so that an open input will
default to max value.
Open input detection
time
Immediate detection (max 2 scans)
Overvoltage capability 15V DC continuous at 25 °C
Overall drift with
temperature
50 ppm/°C of span (max)
Cold junction
compensation Range
-20…100 °C
Cold junction
compensator
A-B catalog number 1794-CJC2
Indicators 1 green power status indicator
8 red open input indicators
Flexbus current 40 mA
Power dissipation 3.0 W max @ 31.2V DC
Thermal dissipation Max 10.2 BTU/hr @ 31.2V DC
Keyswitch position 3
General Specifications
External DC power
supply voltage
Voltage range
Supply current
24V DC nom
19.2…31.2V DC (includes 5% AC ripple)
95 mA @ 24V DC
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connections
to this equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Dimensions (with
module installed in
base) HxWxD approx.
94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)
Temperature code, IEC T4
Temperature code,
North American
T4A
Enclosure type rating None (open-style)
Wire size Determined by installed terminal base
Signal conductors
Thermocouple
Millivolt
Wire type
Use appropriate shielded thermocouple wire
(3)
Belden 8761
Shielded on signal ports
Wiring category
(1)
2 - on signal ports
3 - on power ports
Terminal screw torque
for cage-clamp terminal
base
Determined by installed terminal base
Environmental Specifications
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F) (1794-IRT8, 1794-IRT8K)
-20…70 °C (-4…158 °F) (1794-IRT8XT)
Temperature, non-
operating
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock
operating
nonoperating
IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
50 g
Emissions CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF
immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on shielded signal ports
Surge transient
immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on shielded signal ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded
signal ports
Certifications (when product is marked)
(2)
C-UL-US UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC
T4 X)
EN 60079-0; General Requirements (Zone 2)
TUV TÜV Certified for Functional Safety:
up to and including SIL 2
(1)
Use this category information for planning conductor routing as described in Industrial Automation Wiring and
Grounding Guidelines, Allen-Bradley publication 1770-4.1.
(2)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.
(3)
Refer to the thermocouple manufacturer for proper thermocouple extension.