A terminal base may or may not have an I/O module installed.
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC,
IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V
oc
< 5.8V; I
sc
< 400 mA.
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V
oc
< 9.5V; I
sc
< 1 A.
To any IS device with Entity
Concept parameters of
(V
max
, I
max
, C
i
, L
i
) appropriate
for connection to associated
apparatus with Entity Concept
parameters listed in Table 2.
1797-IE8
or
1797-IE8NF
16
Shield Connection Only
50
51
35
34
V
max
=5.8V
I
max
=400 mA
C
i
=1350 nF
L
i
=negligible
V
max
=9.5V
I
max
=1 A
C
i
=negligible
L
i
=negligible
Male Bus
Connector
33
40
41
42
43
44
45
0 (+)
Female Bus
Connector
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (V
max
, I
max
, C
i
, L
i
)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in Table 1.
1 (sig)
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
2 (-)
4 (+)
5 (sig)
6 (-)
8 (+)
9 (sig)
10 (-)
12 (+)
13 (sig)
14 (-)
17 (+)
18 (sig)
19 (-)
21 (+)
22 (sig)
23 (-)
25 (+)
26 (sig)
27 (-)
29 (+)
30 (sig)
31 (-)