Rockwell-automation 20-750-BNETIP BACnet/IP Option Module Instrukcja Użytkownika Strona 30

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 29
30 Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter 3 Configuring the Option Module
Figure 4 - Edit Fault Action HIM Screens
Changes to these parameters take effect immediately. A reset is not required.
If communication is disrupted and then is re-established, the drive will
automatically receive commands over the network again.
Setting the Fault Configuration Parameters
When setting Host Parameters 33 - [Comm Flt Action] and 34 - [Idle Flt
Action] to ‘Send Flt Cfg, the values in the following parameters are sent to the
drive after a communication fault and/or idle fault occurs. You must set these
parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is not required.
Option Module Host Parameter Description
Parameter 37 - [Flt Cfg Logic] A 32-bit value sent to the drive for Logic Command.
Parameter 38 - [Flt Cfg Ref] A 32-bit REAL (floating point) value sent to the drive for
Reference.
ESC
ENTER
Stopped
0.00 Hz
AUTO
▲▼
Edit Idle Flt Action
Fault 0
0<<4
ESC
ENTER
Stopped
0.00 Hz
AUTO
▲▼
Edit Comm Flt Action
Fault 0
0<<4
Przeglądanie stron 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 87 88

Komentarze do niniejszej Instrukcji

Brak uwag