B-4 Adapter Parameters
20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P
24 [DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.
Default: xxx0 0001
Bit Values: 0 = I/O disabled
1 = I/O enabled
Type: Read/Write
Reset Required: Yes
25 [DPI I/O Act]
Displays the I/O that the adapter is actively
transmitting. The value of this parameter will usually be
equal to the value of Parameter 24 - [DPI I/O Cfg].
Default: xxx0 0001
Bit Values: 0 = I/O disabled
1 = I/O enabled
Type: Read Only
26 [Flt Cfg Logic]
Sets the Logic Command data that is sent to the drive
if Parameter 23 - [Comm Flt Action] is set to “4”
(Send Flt Cfg) and communications are disrupted.
The bit definitions will depend on the product to which
the adapter is connected. See Appendix C or the
documentation for the drive being used.
Default: 0000 0000 0000 0000
Minimum: 0000 0000 0000 0000
Maximum: 1111 1111 1111 1111
Type: Read/Write
Reset Required: No
27 [Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
Parameter 23 - [Comm Flt Action] is set to “4” (Send
Flt Cfg) and communications are disrupted.
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses a 16-bit
Reference, the most significant word of
this value must be set to zero (0) or a
fault will occur.
28
29
30
31
32
33
34
35
[Flt Cfg A1 In]
[Flt Cfg A2 In]
[Flt Cfg B1 In]
[Flt Cfg B2 In]
[Flt Cfg C1 In]
[Flt Cfg C2 In]
[Flt Cfg D1 In]
[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the drive if
Parameter 23 - [Comm Flt Action] is set to “4” (Send
Flt Cfg) and communications are disrupted.
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses 16-bit
Datalinks, the most significant word of
this value must be set to zero (0) or a
fault will occur.
36 [Web Enable]
Displays the setting of the adapter Web Pages Switch
(SW2 in Figure 2.1
) when the adapter was last reset.
Default: 0 = Disabled
Values: 0 = Disabled
1 = Enabled
Type: Read Only
Parameter
No. Name and Description Details
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A
Cmd/Ref
Default x x x 0 0 0 0 1
Bit 76543210
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A
Cmd/Ref
Default x x x 0 0 0 0 1
Bit 76543210