12 PowerFlex® DC Drive - Frame B Field SCR Module
Step 4: Remove the Field
Board and Existing Field
SCR Module
1. Remove the wires from connectors UF, UF1, VF and VF1.
2. Remove the six screws and washers that secure the Field board to the
Field SCR and Dual Diode Modules and remove the Field board.
3. Remove the two screws and washers that secure the existing Field SCR
module to the heatsink and remove the module from the drive.
=
Remove screws
and washers
Remove wires
Remove screws
and washers
Remove screws
and washers