Installation InstructionsPowerFlex® DC Drive - Frame C Cooling Fan What This Kit Includes• Cooling fan• Fan cover screen• Two screws• Fan terminal bl
Publication 20P-IN031A-EN-P - March 2009Copyright © 2009 Rockwell Automation. All rights reserved. Printed in USA.www.rockwellautomation.comAmericas:
2 PowerFlex® DC Drive - Frame C Cooling Fan Step 1: Remove Power from the Drive1. Remove and lock-out all incoming power to the drive. Step 2: Remove
PowerFlex® DC Drive - Frame C Cooling Fan 3 3. Loosen, but do not remove, the screws that secure the top cover to the drive, then slide the cover up a
4 PowerFlex® DC Drive - Frame C Cooling Fan 5. Carefully disconnect the cables from connectors XFCD and XR on the Control board.6. Loosen the two capt
PowerFlex® DC Drive - Frame C Cooling Fan 5 7. Disconnect the cable from connector XSW on the Switching Power Supply board and lower the Control EMI s
6 PowerFlex® DC Drive - Frame C Cooling Fan Step 3: Remove the Existing Cooling Fan1. The cooling fan terminal block is located below the internal Arm
PowerFlex® DC Drive - Frame C Cooling Fan 7 3. Remove the screw that secures the ground wire to the fan housing and remove the ground wire. 4. Remove
8 PowerFlex® DC Drive - Frame C Cooling Fan Step 4: Install the New Cooling FanInstall the new cooling fan in reverse order of removal as detailed in
PowerFlex® DC Drive - Frame C Cooling Fan 9 Step 5: Replace the Protective Covers and Documenting the Change1. Replace the protective covers in the re