• Output leads from the power-line filter to the Dataliner must be 10 cm (4 in.) or
less.
• Both Dataliner and power-line filter must be connected to a low impedance earth
ground
• All parts of the grounding system must be connected together with low
impedance connections. Keep all ground connections as short as possible
• Power-line filter must be connected to earth ground before connecting the power
source.
• Do not run signal wiring and power wiring in the same conduit.
• When control or communication wires must cross, they should cross at an angle
as close to 90 degrees as possible.
• Follow Dataliner display shielded cable requirements as specified in the user
manual.
• Make sure cable shielding connections and terminations are connected as
specified in the appropriate Dataliner User Manual.
• Keep the filter line side leads well separated from the load side leads.