Chapter 13
Creating Alarm Screens
135
4. Enter a screen number.
The screen builder for an alarm screen is displayed.
5. Enter the alarm message text. If you are entering a display field, press
[F1] where you want the field positioned. Refer to Chapter 7 for
information on how to setup a display field.
6. If you want to set an acknowledge bit at the controller when an operator
acknowledges an alarm, press [F3].
You are prompted for the acknowledge bit register information.
Register Information Enter
Register Number
The register number you want to write to when the
operator acknowledges the alarm screen.
Bit Number
The bit number within the register you want to write
to when the operator acknowledges the alarm
screen.
Send 1 or 0 Value to be sent to acknowledge bit.
7. Press [F9] when the screen is completed.