Connect AC Power
The electrical rating for the PanelView 600 terminal is shown below.
The PanelView 600 terminal is an IEC 1131-2 Equipment Class I device and requires
you to connect the (Protective Earth) terminal to an earth conductor.
To connect AC power to the PanelView 600 terminals:
1. Secure the AC power wires to the L1 and L2N screws on the terminal block.
2. Secure the Earth Ground/Protective Earth wire to the screw on the
terminal block.
Terminal Type Supply Voltage Power Consumption
PV600 85…240V AC, 47…63 Hz 60 VA maximum
ATTENTION
The PanelView 600 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
Do not apply power to the terminal until all wiring connections have been made.
Failure to do so may result in electrical shock.
WARNING
Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be non-hazardous.
ATTENTION
Improper wiring of the power terminals may result in voltage at the
communication connector shells. Refer to the following figure when wiring.