PanelView 600 Terminals 11
Publication 2711-IN010G-EN-P - February 2009
Connect AC Power
The electrical rating for the PanelView 600 terminal is shown below.
The PanelView 600 terminal is an IEC 1131-2 Equipment Class I device and requires
you to connect the (Protective Earth) terminal to an earth conductor.
To connect AC power to the PanelView 600 terminals:
1. Secure the AC power wires to the L1 and L2N screws on the terminal block.
2. Secure the Earth Ground/Protective Earth wire to the screw on the
terminal block.
Terminal Type Supply Voltage Power Consumption
PV600 85…240V AC, 47…63 Hz 60 VA maximum
ATTENTION
• The PanelView 600 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
• Do not apply power to the terminal until all wiring connections have been made.
Failure to do so may result in electrical shock.
WARNING
Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be non-hazardous.
ATTENTION
Improper wiring of the power terminals may result in voltage at the
communication connector shells. Refer to the following figure when wiring.