Rockwell Automation Publication 193-UM015B-EN-P - June 2014 241
Metering and Diagnostics Chapter 7
L3 Percent FLA
L3 Percent FLA (Parameter 49) reports the L3 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L3 Percent FLA = L3 Current / Full Load Amps
Table 252 - L3 Percent FLA (Parameter 49)
Average Percent FLA
Average Percent FLA (Parameter 50) reports the average current in comparison
to the active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
Average Percent FLA = Average Current / Full Load Amps
Table 253 - Average Percent FLA (Parameter 50)
Ground Fault Current
Ground Fault Current (Parameter 51) reports the ground fault current measured
by the internal core balanced current transformer of the E300 Electronic
Overload Relay Sensing Module or external core balanced current transformer.
Table 254 - Ground Fault Current (Parameter 51)
Default Value 0.0
Minimum Value 0.0
Maximum Value 1000.00
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units %
Default Value 0.0
Minimum Value 0.0
Maximum Value 1000.00
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units %
Default Value 0.0
Minimum Value 0.0
Maximum Value 99.99
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 100
Units Amps