B-6 DeviceNet Objects
Services
13 Produced Cnxn
Path Length
Get UINT Number of bytes in the produced connection path
attribute
14 Produced Cnxn
Path
Get ARRAY of
UINT
Path information of the desired assembly instance
(Def. 1)
15 Consumed Cnxn
Path Length
Get UINT Number of bytes in the consumed connection path
attribute
16 Consumed Cnxn
Path
Get ARRAY of
UINT
Specifies the application object to receive the data
consumed by this application
17
Production inhibit
time
Get/Set
UINT
Defines minimum time between new data
production for COS connections
Attr.
ID
Attribute Access Data type Description
Service Code Service Name Description
0E
hex
Get_Attribute_Single Returns the value of an attribute
10
hex
Set_Attribute_Single Changes the value of an attribute
05
hex
Reset Reset
16
hex
Save Save
Komentarze do niniejszej Instrukcji